080
1: not save
Once power on, the keypad and terminal
frequency increment will be initialized to 0.
LED tens digit: keep when stop
0: keep when stop
When the VFD stops running, the frequency
set value stays the last modified value.
1: not keep
When the VFD stops running, the set
frequency returns to F0.12.
LED hundreds digit: UP/DOWN
frequency adjustment
0: invalid
1: valid
When valid, operating with key ,
terminal UP/DOWN can achieve the positive
or negative adjustment of the frequency.
LED hundreds digit: UP/DOWN
frequency adjustment
0: invalid
1: valid
When valid, operating with key ,
terminal UP/DOWN can achieve the positive
or negative adjustment of the frequency.
▲ / ▼
▲ / ▼
When frequency channel is defined as digital
given 1 (principle and auxiliary frequency
source are both 0), this function parameter
is initial setting frequency given by keypad
digital frequency.
F0.12
Frequency source digital setting 1
0.00Hz ~【F0.16】upper
limit frequency
50.00
LED units digit: power down save
0: save
Once power on, the keypad and terminal
frequency increment will be initialized to
the value saved in EEPROM when power
down last time.
1: not save
Once power on, the keypad and terminal
frequency increment will be initialized to 0.
LED tens digit: keep when stop
0: keep when stop
When the VFD stops running, the frequency
set value stays the last modified value.
1: not keep
When the VFD stops running, the set
frequency returns to F0.12.
F0.11
Digital frequency set 2 control
000 ~ 111
000
▲ / ▼
▲ / ▼
4.2 Detailed Function Description
When frequency channel is defined as digital
given 2 (principle and auxiliary frequency
source are both 1), this function parameter is
initial setting frequency given by VFD terminal.
F0.13
Frequency source digital setting 2
0.00Hz ~【F0.16】upper
limit frequency
50.00
K is the weight coefficient of auxiliary
frequency source, valid when F0.09 is 1 ~ 8.
F0.14
Auxiliary frequency source weight
coefficient K setting
0.01 ~ 10.00
1.00
F0.15
Max. Output Freq.
Low freq. stage: MAX{50.00,
【F0.16】}~ 300.0
High freq. stage: MAX{50.00,
【F0.16】}~ 3000.0
50.00