F5 Group - VF Control Parameters
Function
Code
Name
Set Range
Minimum
Unit
Factory
Default Modification
F5.17
VF curve max.
voltage of half
separation mode
0.0 ~ 100.0%*rated voltage of motor
note: this voltage represents output
voltage of VFD
0.1%
80.0%
×
F5.18
controller
adjustment cycle
of voltage closed
loop output
0.01 ~ 10.00s
0.01s
0.10
×
F5.19 Voltage rising time 0.1 ~ 3600.0s
note: this parameter is only valid for
open loop output mode of complete
separated voltage
0.1s
10.0
○
F5.20 Voltage declining
time
0.1s
10.0
○
F5.21
Voltage feedback
disconnection
treatment
0: alarm and keep running with the
voltage of disconnection
moment
1: alarm and keep running with
decreased voltage of amplitude
limiting value
2: protection action and free stop
1
0
×
F5.22
Detection value of
voltage feedback
disconnection
0.0 ~ 100.0%*rated voltage of motor 0.1%
2.0%
○
F5.23
Detection time of
voltage feedback
disconnection
0.0 ~ 100.0s
0.1s
10.0
○
F5.24
Limit voltage of
voltage feedback
disconnection
0.0 ~ 100.0%*rated voltage of motor
note: this voltage represents
the output voltage of VFD, and
reasonable setting of this parameter
could prevent machine damage
resulting from voltage overshoot at
disconnection moment.
0.1%
80.0%
○
4.1 Function Code