3.2 LED and Indicator Light Description:
Item
Function Description
Display
Functicn
Digital Display Display current run status parameter and set parameter.
LED
Indicator
Hz、A、V Displayed physical quantity unit (current A, voltage V, frequency Hz)
ALM
Alarm indicator light, indicate that the VFD is in over current or over
voltage suppressing status or failure alarm status currently.
FWD
This indicator light tums green when the VFD is in forward running status.
REV
This indicator light tums red when the VFD is in reverse running status.
REMOTE Remote control indicator.
Table 3-1 LED and Indicator Light Description
Item
Function Description
LED
Indicator
A
Current displayed parameter is current with unit of A, LED indicator light A is on
V
Current displayed parameter is voltage with unit of V, LED indicator light V is on
Hz
Current displayed parameter is frequency with unit of Hz, LED indicator light Hz is on
%
Current displayed parameter is percentage, LED indicator light Hz and V are on
r/min Current displayed parameter is rotational speed, LED indicator light Hz and A are on
m/s Current displayed parameter is linear velocity, LED indicator light V and A are on
℃
Current displayed parameter is temperature, LED indicator light V, A and Hz are on
Table 3-2 Unit Indicator Light Description
3.3 Monitoring Parameter Display
Keypad display status is classified as power-on initialization display, function code and
monitoring parameters display, malfunction alarm status display, run status parameters display.
After power-on, LED will display "P.OFF", then enter setting frequency display status.
When the VFD is stopped, the keypad displays stopped state monitoring parameters, factory
setting is digital setting frequency. As is shown in figure 3-2, unit indicator light reminds that the
unit of current displayed parameter is Hz.
Press key , different monitoring parameters in stopped state can be displayed circularly
(default setting in sequence is main setting frequency, bus voltage. Other monitoring parameters
can be set to display by function code FE.10 ~ FE.11, for details see function code table
FE.10 ~ FE.11); or without pressing , but set tens place of FE.12 as 1 (alternate display of
main and secondary parameters), and the stopped state monitoring parameters will display
circularly every other second automatically; also enter monitoring menu by pressing , and
check each monitoring parameter by , and .