070
4.1 Function Code
FD Group - Pump Use Parameter
Function
Code
Name
Set Range
Minimum
Unit
Factory
Default Modification
FD.00 Special function of
software
0: General function
1: Solar use for pump
2: constant pressure water
supply use
Note: When Fd.00 = 2, set
sensor range at F8.25 and
pressure at F8.26.
1
0
×
FD.01 MPPT upper limit voltage 380V:【Fd.01】~ 1000 537V
220V:【Fd.01】~ 500 311V
1V
Depending
on model
○
FD.02 MPPT lower limit voltage 380V: 0 ~【Fd.00】 350V
220V: 0 ~【Fd.00】 200V
Depending
on model
Depending
on model
○
FD.03 Lowest running frequency
when yielding water
0.00Hz ~【F0.16】
0.01
20
○
FD.04
Water shortage
detection current ratio
corresponding to no-load
current
80.0 ~ 300.0%*【F2.10】
0.1%
150
○
FD.05 Water shortage detection
time
0 ~ 250s
1
10
○
FD.06 Power on auto start delay 0 ~ 65535s
1
0
○
FD.07 Antifreeze function
0: turn off
1: turn on, clock in second
2: turn on, clock in minute
1
0
×
FD.08 Antifreeze action interval 0 ~ 9999s/min
1s/min
300
○
FD.09 Antifreeze protection
action frequency
0.00 ~ upper limit frequency 0.1Hz
10.00
○
FD.10 Antifreeze protection
action time
0 ~ 9999s/min
1s/min
60
○
FD.11 High pressure alarm
setting value
Pressure setting ~ sensor
range
0.1Bar
9.0
○
FD.12 Low pressure alarm
setting value
0.0 ~ water shortage
detection threshold
0.1Bar
0.0
○
FD.13 Abnormal pressure alarm
delay time
0 ~ 65535s
Note: high pressure and low
pressure alarm delay time
0.1s
3
○
FD.14 On-line function selection 0: invalid 1: valid
1
0
○
FD.15 Rotation interval
0 ~ 65535H
1H
72
○