110
This function code defines digital output
terminal and the delayed time from relay
condition changing to output changing.
F7.14
Y1 output delay time
0.0 ~ 100.0s
0.0
F7.15
Y2 output delay time
0.0 ~ 100.0s
0.0
F7.16
R1 output delay time
0.0 ~ 100.0s
0.0
F7.17
R2 output delay time
0.0 ~ 100.0s
0.0
0: no output
1: VFD forward running
The indicator signal output when the VFD is
in forward running.
2: VFD reverse running
The indicator signal output when the VFD is
in reversing running.
3: fault output
The indicator signal output when the VFD
fault occurs.
4: freq./speed level detection signal (FDT1)
Refer to F7.24 ~ F7.26 function description.
F7.18
Open collector output terminal Y1
0 ~ 99
0
F7.19
Open collector output terminal Y2
0 ~ 99
0
F7.20
Programmable relay R1 output
0 ~ 99
3
F7.21
Programmable relay R2 output
0 ~ 99
0
F7.13
reserved
—
0
5: freq./speed level detection signal (FDT2)
Refer to F7.27 ~ F7.29 fuction description.
6: freq./speed arrival signal (FAR)
Refer to F7.23 function description.
7: indicator during zero-speed running
The indicator signal output when VFD is still
in running state and output frequency is
0.00Hz.
8: upper limit arrival of output frequency
The indicator signal output when VFD
output frequency reached its upper limit.
9: lower limit arrival of output frequency
The indicator signal output when VFD
output frequency reached its lower limit.
10: lower limit arrival of preset frequency
The signal is given if the preset frequency
is lower than lower limit during VFD
running.
11: pre-alarm signal of overload
The signal is given after alarm-delay time
(FA.13) if the output current is higher than
overload pre-alarm level (FA.12).
12: counter detection signal output
The indicator signal is given when counter
detection value arrives, and it is cleared
when reset value of counter arrives. See
F7.33.
13: counter reset signal output
The indicator signal is given when counter
reset value arrives. See F7.32.
14: driver ready 1
This signal is output when the driver has
no fault, its bus voltage is normal, the start
prohibit function is disabled, so that the
driver is ready to start for direct command.
(not including run inverter).
4.2 Detailed Function Description