140
0: allow all parameters to be modified (some
are not during operation)
1: only allow F0.12, F0.13 and FE.14 to be
modified
2: only allow PE.14 to be modified
FE.14
write-protect
0 ~ 2
0
0: disabled
1: parameters upload to operation panel
If it is set at 1 and confirmed, the driver will
display CP-1, and upload all function code
parameters from control panel to EEPROM
in operation panel for storage.
2: all function code parameters download to
the driver
If it is set at 2 and confirmed, the driver will
display CP-2, and download all function
code parameters from operation panel
except factory parameter to memory in
main control panel, and refresh EEPROM.
3:download all function code parameters
except motor parameters to the driver
If it is set at 3 and confirmed, the keypad will
display CP-3, and the driver will download
all function code parameters (except motor
parameters and factory parameters) from
operation panel to memory in main control
panel, and refresh EEPROM.
FE.15
Parameter copy function
0 ~ 3
0
4.2 Detailed Function Description
FF Factory Parameter
FF.00
Factory password
0 ~ 65535
0
FF.02
Model
0 ~ 30
Depending
on model
FF.04
Rated voltage
0 ~ 999V
380
FF.01
Reserved
Reserved
0
FF.03
Rated power
0.4 ~ 999.9
Note: This pamameter
only can be read.
Depending
on model
FF.06
Dead zone time
3.2 ~ 10.0µs
Depending
on model
FF.08
Software undervoltage point
220V: 0V ~ 280V 180V
380V: 0V ~ 440V 320V
Depending
on model
FF.05
Rate current
0.1 ~ 6553.5A
Depending
on model
FF.07
Software overvoltage point
220V: 0V ~ 450V 400V
380V: 0V ~ 850V 800V
Depending
on model