058
4.1 Function Code
F9 Group - MS and PLC Running, Traverse and Fixed Length Control
Function
Code
Name
Set Range
Minimum
Unit
Factory
Default
Modification
F9.00 PLC running
mode
0: stop after single cycle
1: retain value after single cycle
2: continuous cycle of limited times
3: continuous cycle
1
0
×
F9.01 Input mode of
PLC running
0: auto
1: manually input via defined
multi-function terminal
1
0
×
F9.02
PLC running
state saving after
power off
0: not save
1: save the stage and frequency
when power off
1
0
×
F9.03 PLC restart mode
0: restart from the first stage
1: start from the stage where the
driver stops (fault)
2: start from the stage where the
driver stops(fault) at the recorded
frequency
1
0
×
F9.04 Limited times of
continuous cycle 1 ~ 65535
1
1
○
F9.05 Unit of PLC
running time 0: s 1: m
1
0
×
F9.06 MS frequency 0 -upper limit Freq. ~ upper limit
Freq.
0.01Hz
5.00
○
F9.07 MS frequency 1 -upper limit Freq. ~ upper limit
Freq.
0.01Hz
10.00
○
F9.08 MS frequency 2 -upper limit Freq. ~ upper limit
Freq.
0.01Hz
15.00
○
F9.09 MS frequency 3 -upper limit Freq. ~ upper limit
Freq.
0.01Hz
20.00
○
F9.10 MS frequency 4 -upper limit Freq. ~ upper limit
Freq.
0.01Hz
25.00
○
F9.11 MS frequency 5 -upper limit Freq. ~ upper limit
Freq.
0.01Hz
30.00
○
F9.12 MS frequency 6 -upper limit Freq. ~ upper limit
Freq.
0.01Hz
40.00
○
Содержание SKI600
Страница 3: ......
Страница 4: ...88888 Operating Instruction Manual High performance Vector Inverter ...
Страница 179: ......
Страница 180: ......