069
4.1 Function Code
FC Group - Advanced Function and Performance Parameters
Function
Code
Name
Set Range
Minimum
Unit
Factory
Default
Modification
FC.24 Jog priority
0: disabled
1: the jog has the highest
priority during the driver
operation
1
0
×
FC.25 Special function
LED one's place: A02 and
D0 output selection
0: A02 enabled
1: D0 enabled
LED ten's place: OC
function (reserved)
0: disabled
1: enabled
LED hundred's place: OU1
function (reserved)
0: disabled
1: enabled
LED thousand's palce:
reserved
1
10
×
FC.26 Oscillation suppression
upper limit freq.
0.00 ~ 300.00Hz
0.01
50.00
○
FC.27 Oscillation suppression
coefficient
1 ~ 500
1
50
○
FC.28 Oscillation suppression
voltage
0.0 ~ 25.0%*motor rated
voltage
0.1%
5.0
○