073
4.1 Function Code
FE Group - Panel Function Setting and Parameter Management
Function
Code
Name
Set Range
Minimum
Unit
Factory
Default
Modification
FE.14 Write-protect
0: allow all parameters to
be modified some are not
during operation)
1: only allow F0.12, F0.13
and F0.14 to be modified
2: only allow FE.14 to be
modified
Note: these above
limitations are invalid to
this function code and
F0.00
1
0
○
FE.15 Parameter copy function
0: disabled
1: parameters upload to
operation panel
2: all function code
parameters download to
the driver
3: download all function
code parameters except
motor parameters to the
driver
Notel: when selecting
parameters to download,
the software will check if it
is in accordance with the
driver power specification;
if not, all the parameters
relevant to model will not
be changed.
Note2: only keyboard KB2
has copy function, copy
with normal keyboard will
increase fault.
1
0
×
Содержание SKI600
Страница 3: ......
Страница 4: ...88888 Operating Instruction Manual High performance Vector Inverter ...
Страница 179: ......
Страница 180: ......