4.2 Detailed Function Description
FD Pump Use Parameter
FD.00
Special function of software
0: General function
1: Solar use for pump
2: constant pressure water
supply use
Note: When Fd.00 = 2, set
sensor range at F8.25 and
pressure at F8.26.
0
FD.08
Antifreeze action interval
0 ~ 9999s/min
300
FD.03
Lowest running frequency when
yielding water
0.00Hz ~【F0.16】
20
FD.11
High pressure alarm setting value
Pressure setting ~ sensor
range
9.0
FD.01
MPPT upper limit voltage
380V:【Fd.01】~ 1000
537V
220V:【Fd.01】~ 500
311V
Depending
on model
FD.09
Antifreeze protection action
frequency
0.00 ~ upper limit
frequency
10.00
FD.04
Water shortage detection current ratio
corresponding to no-load current
80.0 ~ 300.0%*【F2.10】
150
FD.12
Low pressure alarm setting value
0.0 ~ water shortage
detection threshold
0.0
FD.02
MPPT lower limit voltage
380V: 0 ~【Fd.00】 350V
220V: 0 ~【Fd.00】 200V
Depending
on model
FD.10
Antifreeze protection action time
0 ~ 9999s/min
60
FD.05
Water shortage detection time
0 ~ 250s
10
FD.13
Abnormal pressure alarm delay time
0 ~ 65535s
Note: high pressure and low
pressure alarm delay time
3
FD.06
Power on auto start delay
0 ~ 65535s
0
FD.14
On-line function selection
0: invalid
1: valid
0
FD.07
Antifreeze function
0: turn off
1: turn on, clock in second
2: turn on, clock in minute
0
FD.15
Rotation interval
0 ~ 65535H
72