123
Notice
1: A stage is ineffective if its run time is set
to 0.
2: The control of PLC process including
input, pause and reset can be realized via
terminal. See function definition of F7
terminal.
3: PLC operation direction is determined
by plus/minus of frequency and operation
command together. The running direction
of motor can be changed by external
command.
0: disabled
1: enabled
F9.55
Traverse control
0 ~ 1
0
0: auto
1: terminal config. (manually)
When F9.56 is set at 1, if multi-function
terminal selects function NO.35, the driver
will enter traverse mode. Otherwise,
traverse is enabled.
F9.56
Input method of traverse mode
0 ~ 1
0
0: fixed amplitude
The reference value of amplitude is max.
frequency F0.15.
1: varied amplitude
The reference value of amplitude is
specified channel frequency.
F9.57
Amplitude control
0 ~ 1
0
0: start to the state before stop
1: just restart, no other requirement
F9.58
restart method of traverse mode
0 ~ 1
0
0: save
1: not save
The traverse state parameters will be
saved when poweroff. This function is only
effective when "start to the state before
stop" mode is selected.
F9.59
Save traverse state upon power
failure
0 ~ 1
0
F9.54
reserved
reserved
0
4.2 Detailed Function Description
F9.60
Preset traverse frequency
0.00Hz ~ upper limit
10.00
F9.61
Preset traverse frequency hold time
0.0 ~ 3600.0s
0.0
These above function codes defined run
frequency before entering traverse mode or
when exiting traverse mode and hold time
of the frequency. If F9.61 ≠ 0, the driver will
run at preset traverse frequency when start,
and enter traverse mode after preset traverse
frequency hold time.