154
Analysis of this segment data:
01H address of the driver
13H write function code
000CH start address, equivalent to F0.12 of control panel
1388H parameter value
0322H attribute value
0000H min.value
1388H max.value
2831H 16 bits of CRC check code
Example:
Name
Frame format
Read parameter value of
F0.12
Send frame: 01H 13H 000CH 0001H 85CAH
Return frame: 01H 13H 02H 1388H B1D2H
Read parameter value +
attribute value of F0.12
Send frame: 01H 13H 000CH 0002H C5CBH
Return frame: 01H 13H 04H 1388H 0322H FCE4H
Read parameter value +
attribute value + min.value
of F0.12
Send frame: 01H 13H 000CH 0003H 040BH
Return frame: 01H 13H 06H 1388H 0322H 0000H 628BH
Read parameter value + min.
value + max.value of F0.12
Send frame: 01H 13H 000CH 0004H 45CBH
Return frame: 01H 13H 08H 1388H 0322H 0000H 1388H 2831H
Communication Protocol