056
4.1 Function Code
F8 Group - PID Control Parameters
Function
Code
Name
Set Range
Minimum
Unit
Factory
Default
Modification
F8.05 Proportional gain
KP1
0.01 ~ 100.00
0.01
2.5
○
F8.06 Integral time Ti1 0.01 ~ 10.00s
0.01s
0.10
○
F8.07 Derivative time
Td1
0.01 ~ 10.00s
0.00: no derivation
0.01s
0.00
○
F8.08 Sampling cycle T 0.01 ~ 10.00s
0.00: auto
0.01s
0.10
○
F8.09 Error limit
0.0 ~ 100.0%
0.1%
0.0%
○
F8.10 Close-Ioop preset
freq.
0.00 ~ upper limit freq.
0.01Hz
0.00
○
F8.11 Preset freq. hold
time
0.0 ~ 3600.0s
0.1s
0.0
×
F8.12 Sleep mode
0: disabled
1: sleep when feedback pressure
exceeding or lower than sleep
threshold
2: sleep when feedback pressure
and output frequency are stable
1
1
×
F8.13 Stop method of
sleep mode
0: decelerate to stop
1: coast to stop
1.00
0
○
F8.14
Deviation limit of
feedback when
entering sleep
state compared
with set pressure
0.0 ~ 10.0%
Note: this parameter is only valid
to the second sleep mode.
0.1%
0.5%
○