4.1 Function Code
F1 Group - Auxiliary Operating Parameters
Function
Code
Name
Set Range
Minimum
Unit
Factory
Default
Modification
F1.00 Start mode
0: start at start frequency
1: DC b start at start
frequency
2: start with speed tracking
1
0
×
F1.01 Start frequency 0.00 ~ 50.00Hz
0.01Hz
1.00
○
F1.02 Start frequency hold
time
0.0 ~ 100.0s
0.1s
0.0
○
F1.03 DC brake current at
startup
0.0 ~ 150.0% *rated current
of motor
0.1%
0.0%
○
F1.04 DC brake time at
startup
0.0 ~ 100.0s
0.1s
0.0
○
F1.05 Accelerating and
decelerating mode
0: linear Acc/Dec mode
1: S curve Acc/Dec mode
1
0
×
F1.06 Time ratio of initial
segment in S curve 10.0 ~ 50.0%
0.1%
20.0%
○
F1.07 Time ratio of ending
segment in S curve 10.0 ~ 50.0%
0.1%
20.0%
○
F1.08 Stop mode
0: Decelerate to stop
1: coast to stop
1
0
×
F1.09 Frequency threshold
of DC brake
0.00 ~【F0.16】upper limit
frequency
0.01Hz
0.00
○
F1.10 DC brake delay time 0.0 ~ 100.0s
0.1s
0.0
○
F1.11 DC brake current 0.0 ~ 150.0% *rated current
of motor
0.1%
0.0%
○
F1.12 DC brake time at stop 0.0 ~ 100.0s
0.1s
0.0
○
F1.13 Acc time 2
0.1 ~ 3600.0s
0.4 ~ 4.0KW 7.5s
5.5 ~ 30.0KW 15.0s
37.0 ~ 132.0KW 40.0s
160.0 ~ 630.0KW 60.0s
0.1
Depending
on model
○
F1.14 Dec time 2
0.1
Depending
on model
○
F1.15 Acc time 3
0.1
Depending
on model
○
F1.16 Dec time 3
0.1
Depending
on model
○
F1.17 Acc time 4
0.1
Depending
on model
○
F1.18 Dec time 4
0.1
Depending
on model
○