112
braking action. Refer to function code
FC.21 for corresponding setting.
29: torque limiting
This signal is sent during torque control.
Refer to F4.10 ~ F4.23.
30: over torque
This indicator signal is sent according to
F4.22 ~ F4.24 setting.
31: auxiliary motor 1
32: auxiliary motor 2
The function of constant pressure water
supply can be realized by auxiliary motor
1,2 and PID function module.
33: total operating time arrival
This signal is sent when the operating limit
time (FC.11) arrives.
34 ~ 49: multi-speed or PLC running segment
The output terminal function 34 ~ 49
items correspond to 0 ~ 15 segments of
multi-speed or simple PLC, and this signal
is sent when the corresponding segment
of output terminal setting arrives.
50: VFD running indication
Indication signal output when VFD is in in
forward/reverse running state.
51: temperature arrival indication
This signal is sent when actual temperature
(d-33 ~ d-34) is higher than threshold
temperature (FA.14).
52: indicate when VFD stops or runs at zero
speed
53: reserved
54: reserved
55: communication setting
56: drive ready 2
The same to function of above No.14(driver
ready 1), except this command includes
run inverter.
57: AI1 input over limit
The output indication signal is output
when the value of the analog input AI1
is more than F6.53 (AI1 input voltage
protection upper limit) or less than F6.54
(AI1 input voltage protection lower limit).
58 ~ 99: reserved
F7.22
Effective logic setting of output
terminal (Y1 ~ Y2)
0 ~ 3H
0
Bit0: effective logic definition of Y1 terminal
Bit1: effective logic definition of Y2 terminal
0: positive logic, i.e. Yi terminal is enabled
when it connects with common terminal and
disabled if disconnected.
1: negative logic, i.e. Yi terminal is disabled
whe n it connects with common terminal and
enabled if disconnected.
When F7.22=0, Yi and Y2 terminals are enabled
when they connect with common terminal
and enabled if disconnected.
When F7.22=1, Y1 terminal is disabled when it
connect with common terminal and enabled if
disconnected; Y2 terminal is disabled when it
connect with common terminal and enabled if
disconnected.
When F7.22=2, Y1 terminal is enabled when it
connect with common terminal and disabled
if disconnected; Y2 terminal is disabled when
it connect with common terminal and enabled
if disconnected.
When F7.22=3, Y1 and Y2 terminals are
disabled when they connect to common
terminal and enabled if disconnected.
4.2 Detailed Function Description