Settings to Reduce the Leakage Currents
Via jumpers at the top and the bottom of the device, the FCS01 frequency
converters can for example be adjusted for operation at IT mains and for
reduction of leakage currents.
At the top of the device (mains input)
Fig. 8-18:
Mains input jumper in position "2"
Position
Setting
Effect
0
Operation at the IT mains
1
No effect
2
Standard position (factory setting)
Fig. 8-19:
Jumper position top
At the bottom of the device (motor output)
Fig. 8-20:
Motor output jumper in position "1"