14-4
Additional Information
Rexroth IndraDrive FCS01.1
DOK-INDRV*--FCS01*****-IB01_EN-P
Process Controller Parameter Settings
(Example: setpoint frequency: 50 Hz, control limits: +/- 25%)
P105 (maximum frequency) [Hz]:
[ ]
[ ]
[ ]
×
+
≥
%
100
%
415
.
.
.
.
P
Hz
frq
Setp
Hz
frq
Setp
: Example:
=
×
+
≥
%
100
%
25
50
50
Hz
Hz
62.5 Hz
P400 (Fct. analog input)
:
"
4"
(frequency addition)
P411 (setpoint frequency) [Hz]:
setpoint frequency at 10V at analog input1:
Example
50 Hz
P412 (setpoint process controller):
medium setting PW / factory setting
5 V
(adjust if necessary)
P413 (P controller) [%]:
factory setting
10%
(adjust if necessary)
P414 (I controller) [% / ms]:
recommended
0,1
ms
%
P415 (limi/-) [%]:
controller limitation (see above) Example
25%
of the setpoint value
P416 (ramp before
controller) [s]
:
factory setting
2s
(adjust to control behavior if applicable)
P420 (Fct. digital input 1):
"1"
release right
P421 (Fct. digital input 2):
"40"
actual value PID process controller