Rexroth IndraDrive FCS01.1
Parameterization
11-21
DOK-INDRV*--FCS01*****-IB01_EN-P
Parameter
Setting value / description / note
Device
Supervisor
Parameter
record
-50.00 ... 50.00 V
[ 0.00 ]
This parameter is identical with P402.
P408
Adjustment analog input 2
100%
S
-50.00 ... 50.00 V
[ 10.00 ]
This parameter is identical with P403.
P409
Filter analog input 2
S
1 ... 400 ms
[ 100 ]
This parameter is identical with P404.
P410
Minimum frequency
secondary setpoint values
P
-400.0 ... 400.0 Hz
[ 0.0 ]
This is the minimum frequency which can act upon the setpoint via the secondary
setpoint values.
Secondary setpoints are all frequencies which are additionally supplied to the FC for
further functions.
Actual frequency PID
Frequency addition
Frequency subtraction
Secondary setpoints via BUS
Process controller
min. frequency via analog setpoint (potentiometer)
P411
Maximum frequency
secondary setpoint values
P
-400.0 ... 400.0 Hz
[ 50.0 ]
This is the maximum frequency which can act upon the setpoint via the secondary
setpoint values.
Secondary setpoints are all frequencies which are additionally supplied to the FC for
further functions.
Actual frequency PID
Frequency addition
Frequency subtraction
Secondary setpoints via BUS
Process controller
max. frequency via analog setpoint (potentiometer)
P412
Setpoint process controller
S
P
-10.0 ... 10.0 V
[ 5.0 ]
To specify a fixed setpoint value for the process controller which is to be modified only
rarely.
Only with P400 = 14 ... 16 (process controller). For more details, please refer to
Chapter 14.2, Process Controller.
P413
P quota PID controller
S
P
0.0 ... 400.0 %
[ 10.0 ]
Only effective if the function actual frequency PID has been selected.
The P quota of the PID controller defines the frequency jump in case of a deviation in
respect of the controller difference.
Example: In case of a setting of P413 = 10% and a deviation of 50%, 5% is added to
the current setpoint value.
P414
I quota PID controller
S
P
0.0 ... 300.00
%/ms
[ 1.00 ]
Only effective if the function actual frequency PID has been selected.
In case of a deviation, the I quota of the PID controller will define the frequency
modification in dependence on the time.
P415
D quota PID controller
S
P
Содержание IndraDrive Fc FCS01
Страница 28: ...5 2 Delivery Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Страница 34: ...6 6 Certifications and Types Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Страница 56: ...8 20 Installation Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Страница 88: ...10 4 Commissioning Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Страница 237: ......