12-2
Error Messages
Rexroth IndraDrive FCS01.1
DOK-INDRV*--FCS01*****-IB01_EN-P
Available error messages
Indication at the
standard control
panel
Group
Detail in
P700 / P701
Indication at the comfort
control panel
Cause
•
Remedy
E001
1.0
Overtemperature converter
Error signal from the output stage module (static)
•
Lowering of the environmental
temperature (<50°C or <40°C, also see Chap.
13, Technical Data)
•
Check control cabinet ventilation
E002
2.0
Overtemperature motor
(PTC thermistor)
Only when a digital input
(function 13) has been
programmed.
The motor temperature feeler has triggered
•
reduce motor load
•
increase motor speed
•
use forced ventilation of the motor
2.1
Overtemperature motor
(I
2
t)
Only when I
2
t motor (P535) has
been programmed.
I
2
t motor has responded
•
reduce motor load
•
increase motor speed
3.0
Overcurrent inverter
I
2
t limit has responded, e.g. > 1,5 x I
n
for 60s
(please also note P504)
•
Avoid permanent overload at the frequency converter
output.
3.1
Overcurrent chopper
U
2
t limit for the brake chopper has responded
(please also note P555, P556, P557)
•
Avoid overload at the braking resistor
3.2
Overcurrent derating
monitoring 125%
Derating (power reduction) with f < 2 Hz
•
125% OC level for 50 ms
E003
3.3
Overcurrent derating
monitoring 150%
Derating (power reduction) with f < 2 Hz
•
150% OC level
4.0
Overcurrent module
(Temporary) error signal from the module
•
Localize short circuit or ground fault at the frequency
converter output.
•
Use external output throttle (motor cable is too long)
E004
4.1
Overcurrent module
from current measuring
Output current exceeds the measuring range
•
Localize short circuit or ground fault at the frequency
converter output.
•
Use external output throttle (motor cable is too long)
5.0
Overvoltage DC bus
The frequency converter DC bus voltage is too high.
•
Reduce the recovered energy by means of a braking
resistor.
•
Prolong braking time (P103).
•
Possibly, set the switch-off mode (P108) with a delay
(not for lifting gear)
•
Prolong the quick-stop time (P426)
E005
5.1
Overvoltage mains
Mains voltage too high.
•
Please check 380V-20%...480V+10% / 200...240V
±
10%
Содержание IndraDrive Fc FCS01
Страница 28: ...5 2 Delivery Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Страница 34: ...6 6 Certifications and Types Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Страница 56: ...8 20 Installation Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Страница 88: ...10 4 Commissioning Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Страница 237: ......