Rexroth IndraDrive FCS01.1
Technical Data
13-7
DOK-INDRV*--FCS01*****-IB01_EN-P
Reduced overcurrent based on mains voltage
The FCS01 devices are thermally dimensioned for the rated currents.
This rated current is available with the specified rated voltage. With
deviating rated voltages in the permissible range, please note the
following:
•
Umains<Urated
: With mains voltages below the rated voltage, no
higher currents may be withdrawn to ensure that the dissipated power
remains current.
•
Umains>Urated
: With mains voltages greater than the rated voltage,
a reduction of the permissible output permanent currents takes place
to compensate for the increased switching losses.
320
340
360
380
400
420
440
460
480
0.4
0.5
0.6
0.7
0.8
0.9
1
1.1
1.2
Main voltage [V]
I / I
N
I:
permissible overcurrent
I
N
:
Rated current
Fig. 13-7:
Derating vs. U mains