8-12
Installation
Rexroth IndraDrive FCS01.1
DOK-INDRV*--FCS01*****-IB01_EN-P
X3, System Connection (PE, L1, L2/N, L3)
The frequency converter does not require any special securing at the
power input side. We recommend to use the usual mains fuses (see
Technical Data), and a main switch or contactor.
230V devices of up to 2.2kW may either be operated with 1-phase 230V
(L/N = L1/L2) or with 3-phase 230V (L1/L2/L3).
All 400V devices and devices
≥
3kW must only be supplied with 3-phase
mains voltage (L1/L2/L3). Please refer to Chapter 13, Technical Data, for
a detailed specification.
Fig. 8-13:
System connection
Operation with earth-leakage circuit breakers
The frequency converter FCS01 are dimensioned for the operation with a
30mA a.c.-d.c. earth-leakage current breaker.
If
several
FCS01 frequency converters are operated at an earth-leakage
circuit breaker, the leakage currents must be reduced against PE.
Operation IT Mains
Note:
The FCS01 frequency converter can be used with
IT mains
after adjustment by means of jumpers.
Also refer to Chapter 8 Settings to Reduce the Leakage
Currents.