Rexroth IndraDrive FCS01.1
Indications and Operation of the Function Modules
9-27
DOK-INDRV*--FCS01*****-IB01_EN-P
DeviceNet Module FCC01.1F-DN1-NNNN
DeviceNet is an open communication profile for distributed industrial
automation system. It is based on the CANbus system.
Up to 64 nodes can be connected at one bus system.
Fig. 9-25:
DeviceNet module FCC01.1F-DN1-NNNN
MS (red/green) Module state
DeviceNet status LEDs
NS (red/green)
Mains (bus) state
DS (green)
Module state
Modules status LEDs
DE (red)
Module error
Use the rotating switches NA x 1 and NA x 10 to set the node address
(0..63):
Example: Node adr= 50 Dec = NA x 1 = 0, NA x 10 = 5
If the node address is set to a value greater 63, the value from parameter
515 of the frequency converter is used as a node address.
Set the Baud rate by means of the rotating switch DR
(125kBit/s…500kBit/s). If a value is set in the PGM range, the value from
parameter 514 of the frequency converter is used as a Baud rate.
1
2
3
4
5
Fig. 9-26:
Pin assignment FCC01.1F-DN1
Setting the node ID
Setting the Baud Rate
Connector pin assignment