11-44
Parameterization
Rexroth IndraDrive FCS01.1
DOK-INDRV*--FCS01*****-IB01_EN-P
Parameter
Setting value / description / note
Device
Supervisor
Parameter record
P557
Power braking resistor
S
0.00 ... 20.00
kW
[
0
.00 ]
Continuous power (nominal power) of the resistor for calculating the maximum braking
power.
0.00 =
monitoring deactivated
P558
Magnetization time
S
P
0 / 1 / 2 ... 500
ms
[ 1 ]
The ISD control can only work properly if there is a magnetic field in the motor. For this
reason, DC current is applied to the motor before the start. The duration depends upon the
motor dimension and is automatically set in the FC factory setting.
For time-critical applications, magnetization time can be set or deactivated.
0 =
switched
off
1 =
automatic calculation
2 ... 500 =
correspondingly set time in [ms]
Note:
Excessively small values can reduce dynamics and torque development on
start-up.
P559
DC lag time
S
P
0.00 ... 2.50 s
[ 0.50 ]
After a stop signal and expiry of the brake ramp, a DC current is temporarily applied to the
motor in order to completely deactivate the drive. Depending on mass inertia, the time of
current application can be set via this parameter.
The amount of current depends on the previous braking process (current vector control) or
on the static boost (linear characteristic).
P560
Save to EEPROM
S
0 ... 1
[ 0 ]
0 =
Changes of the parameter settings are lost when the FC is disconnected from the
mains.
1 =
All parameter settings are automatically written into the EEPOM. Thus, they are
retained when the FU is disconnected from the mains.
Note:
When the USS protocol is used to modify parameters, please ensure that the
maximum number of write cycles to the EEPROM (100.000 x) is not
exceeded.
Содержание IndraDrive Fc FCS01
Страница 28: ...5 2 Delivery Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Страница 34: ...6 6 Certifications and Types Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Страница 56: ...8 20 Installation Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Страница 88: ...10 4 Commissioning Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Страница 237: ......