Rexroth IndraDrive FCS01.1
Control Communication - Field Busses and Protocols
15-19
DOK-INDRV*--FCS01*****-IB01_EN-P
Profibus Data Transfer - Sample Telegrams
In the following, the control and parameterization of the converter via the
Profibus is illustrated by way of several sample telegrams.
Activation Disable
→
→
→
→
Ready for Activation
A frequency converter is to be switched from the "activation disable" state
(CTW bit 0 = 0), which is active after the device has been switched on,
into the "ready for activation" state (CTW bit 0 = 1). Parameter record 1 is
valid. Only the PCD channel is taken into consideration.
Procedure:
•
Check status word (STW 0B 70)
•
Generate control word (STW 04 7E)
•
Check response telegram (STW 0A 31)
Details:
Converter status word
→
converter is in
Activation disable
state
9
10
11
12
STW
STW
AV1
AV1
0B
70
00
00
Bit
Value
Value
HEX
Significance
15
0
Parameter record bit 1 off
14
0
Parameter record bit 0 off
13
0
reserved
12
0
0
Counterclockwise rotation off
11
1
Clockwise rotation on
10
0
Value has fallen below comparison
value
9
1
Bus control
8
1
B
Setpoint value = actual value
7
0
No warning
6
1
Activation disable
5
1
No quick-stop
4
1
7
Voltage disabled
3
0
Free of failure
2
0
Disable operation
1
0
Not ready for operation
0
0
0
Not ready for activation
Fig. 15-28: Example telegram
Содержание IndraDrive Fc FCS01
Страница 28: ...5 2 Delivery Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Страница 34: ...6 6 Certifications and Types Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Страница 56: ...8 20 Installation Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Страница 88: ...10 4 Commissioning Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Страница 237: ......