11-30
Parameterization
Rexroth IndraDrive FCS01.1
DOK-INDRV*--FCS01*****-IB01_EN-P
Value
Function
Description
Signal
P433
Fixed frequency 5
P
-400 ... 400 Hz
[ 0 ]
Function description of the parameter, see
P429 >Fixed frequency 1<
P434
Function relay 1
P
The settings 3 to 5 work with a 10% hysteresis; this means that the relay contact closes
(function 11 opens) when the limit value is reached, and opens (function 11 closes)
when the value falls below a value which is lower by 10%.
Setting / function
Relay contact…
with limit value or
function
0 =
no function
open
1 =
external brake,
for controlling a mechanical brake at the
motor. The relay switches at the programmed absolute
minimum frequency. For typical brakes, a setpoint value
delay of 0.2…0.3 s (also see P170) should be programmed.
A mechanical brake may be connected directly at the AC
current side. (Please observe the technical specification of
the relay contact).
closes
2 =
Converter is running
, the closed relay contact signals
voltage at the converter output (U - V - W).
closes
3 =
Current limit
, based on the setting of the nominal motor
current in P203. This value can be adjusted via scaling
(P435).
closes
4 =
Torque current limit
, based on the setting of the motor
data in P203 and P206. Signals a corresponding torque
load at the motor. This value can be adjusted via scaling
(P435).
closes
5 =
Frequency limit
, based on the setting of the nominal
motor frequency in P204. This value can be adjusted via
scaling (P435).
closes
6 =
Setpoint value reached
, indicates that the FC has
completed the frequency increase or reduction. Setpoint
frequency = actual frequency! From a difference of 1 Hz
Setpoint not reached - contact opens.
closes
7 =
Failure,
total failure message, failure is active or not yet
confirmed.
Operative - closes
opens
8 =
Warning
, total warning; a limit value has been reached
which may cause subsequent deactivation of the FC.
opens
9 =
Overcurrent warning
, at least 130% nominal converter
current for 30 sec.
opens
10 =
Motor overtemperature warning:
The motor
temperature is evaluated via a digital input. motor is too
hot. The warning is displayed immediately, the
overtemperature deactivation follows after 2 seconds.
opens
11 =
Torque current limit/current limit active (warning)
,
Limit value in P112 or P536 has been reached. P435 is
insignificant. Hysteresis = 10%.
opens
0 ... 38
[ 1 ]
12 =
Relay through P541 - external control
, the relay can
be controlled via parameter 541 (bit 0) independent of the
FC's current operating status.
closes
Содержание IndraDrive Fc FCS01
Страница 28: ...5 2 Delivery Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Страница 34: ...6 6 Certifications and Types Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Страница 56: ...8 20 Installation Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Страница 88: ...10 4 Commissioning Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Страница 237: ......