190
-L
L
Home switch
Home switch signal
Motion profile
The ORGP signal is active initially, and the motor directly starts homing in negative direction at
low speed.
After reaching the falling edge of the ORGP signal, the motor changes to run in positive
direction at low speed.
After reaching the rising edge of the ORGP signal, the motor stops.
23
)
6098h=25
Home:
home switch
Deceleration point:
home switch
a
)
Deceleration point signal inactive at homing start, not reaching positive limit switch
H
-L
L
Home switch
Home switch signal
Motion profile
The ORGP signal is inactive initially, and the motor starts homing in positive direction at high
speed. If the motor does not reach the limit switch, it decelerates and continues to run in
positive direction at low speed after reaching the rising edge of the ORGP signal. After reaching
the falling edge of the ORGP signal, the motor changes to run in negative direction at low speed,
and stops at the rising edge of the ORGP signal.