4-5
Safe Torque Off
AC890PX AC Drive
Category 3 general requirements are:
A single failure, and any consequential failures, will not lead to loss of the STO safety function.
Failure of more than one component can lead to the loss of the STO safety function.
Most but not all single component failures will be detected. Diagnostic Coverage (DC) is
required to be at least 60% (i.e. the minimum required for ‘low’ diagnostic coverage).
Detected component failures will result in the STO function being applied without intervention
from the user.
The risk associated with the loss of STO safety function caused by multiple failures must be
understood and accepted by the user.
The user must undertake a risk analysis and specify suitable components that, when connected
together, meet the required risk assessment requirements.
Mean Time To Failure (dangerous) (MTTFd) of each STO channel must be ≥ 30 years.
Common Cause Failure (CCF) score must be ≥ 65 according to Annex F of the standard.
Performance Level e:
Average Probability of dangerous Failure per Hour (PFH) must be ≤ 10
-7
Содержание AC890PX Series
Страница 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Страница 25: ...3 4 Installing the Drive AC890PX AC Drive Outline Drawing of AC890PX 132kW 400kW HC471581 page 2 of 2 ...
Страница 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Страница 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Страница 159: ...7 24 The Keypad AC890PX AC Drive Assembly Procedure Mounting Dimensions for the Remote Mounted 6901 Keypad ...
Страница 250: ...Programming D 10 AC890PX AC Drive VALUE INPUT BREAK VALUE INPUT LOSS LEVEL BREAK ENABLE BREAK TYPE UNPROCESSED ...
Страница 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Страница 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...
Страница 391: ...D 151 Programming AC890PX AC Drive Speed Rated Speed No Load Speed synchronous speed Rated Torque Torque ...