![Parker AC890PX Series Скачать руководство пользователя страница 63](http://html1.mh-extra.com/html/parker/ac890px-series/ac890px-series_product-manual_755704063.webp)
3-42
Installing the Drive
AC890PX AC Drive
Setting the Encoder Sign (Closed-Loop Vector Mode)
If you have performed a Stationary Autotune in Closed-loop Vector mode, you should check the encoder direction as follows:
Look and listen to the motion of the motor when the drive is running at a speed demand of between 5 - 10%.
As a test, use the Rotary Controller (
) key on the MMI to increase the speed to about double the original figure. Change the
direction of rotation using the
FWD/REV
control key.
If ENCODER INVERT is correct, the motor will rotate smoothly and will respond to the changes in speed demand and
direction.
If ENCODER INVERT is incorrect, the motor will rotate in a jerky and/or noisy manner. Alternatively, it may rotate
smoothly at a very low speed but not respond to changes in speed demand or direction.
Change the setting of ENCODER INVERT to change the encoder sign.
Change the direction of rotation back to the original direction. Re-set the speed demand.
The encoder sign is now correct for the original motor direction.
If however the direction of the motor is incorrect at this point, then power down the entire drive, wait for 3 minutes (for the dc
link capacitors to discharge) and then swap the motor drive cables M1/U and M2/V. Change the setting of ENCODER
INVERT.
The encoder sign is now correct for the new motor direction.
IMPORTANT
Now perform a SAVE CONFIG to save your new settings. Refer to Chapter 7: “The Keypad” - Quick Save Feature.
Содержание AC890PX Series
Страница 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Страница 25: ...3 4 Installing the Drive AC890PX AC Drive Outline Drawing of AC890PX 132kW 400kW HC471581 page 2 of 2 ...
Страница 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Страница 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Страница 159: ...7 24 The Keypad AC890PX AC Drive Assembly Procedure Mounting Dimensions for the Remote Mounted 6901 Keypad ...
Страница 250: ...Programming D 10 AC890PX AC Drive VALUE INPUT BREAK VALUE INPUT LOSS LEVEL BREAK ENABLE BREAK TYPE UNPROCESSED ...
Страница 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Страница 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...
Страница 391: ...D 151 Programming AC890PX AC Drive Speed Rated Speed No Load Speed synchronous speed Rated Torque Torque ...