D-161
Programming
AC890PX AC Drive
SPEED LOOP 2
SETUP::MOTOR CONTROL::SPEED LOOP 2
Designed for SENSORLESS VEC and CLOSED-LOOP VEC Motor Control Modes.
There are three filters operating on the speed loop torque demand output. They add compensation to the transfer function of the
motor and load. This can improve performance. Use the tuning tool in the DSE 890 Configuration Tool to set these filters
optimally.
Setting the Filter Type to NONE will cause the filter to have no effect. If compensation is required, up to three filters may be
selected in any order and in any combination.
One of the filters is located in the SPEED LOOP function block, the other two filters are located in the SPEED LOOP 2
function block (this block).
The SPEED LOOP function block contains one filter: this is selected by COMPENSATION F1 and COMPENSATN TYPE
(a second parameter COMPENSATION F2 is also used when the compensation type is selected to be
PHASE ADVANCE
).
The SPEED LOOP 2 function block (this block) contains two filters: these are selected by TQ COMP 2 FREQ and
SELECT TQ COMP 2, and also TQ COMP 3 FREQ and SELECT TQ COMP 3.
Parameter Descriptions
SELECT TQ COMP 2
PREF: 163.1
Default: NONE
Range: See below
Selects the type of compensation applied to the torque demand. Refer to Functional Description in the SPEED LOOP
function block for selection details. (
PHASE ADVANCE
is not selectable with this filter)
Enumerated Value
:
Filter
Type
0 : NONE
1 : MAX ATTENUATION
2 : MINIMUM PHASE
3 : NOTCH FILTER
Содержание AC890PX Series
Страница 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Страница 25: ...3 4 Installing the Drive AC890PX AC Drive Outline Drawing of AC890PX 132kW 400kW HC471581 page 2 of 2 ...
Страница 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Страница 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Страница 159: ...7 24 The Keypad AC890PX AC Drive Assembly Procedure Mounting Dimensions for the Remote Mounted 6901 Keypad ...
Страница 250: ...Programming D 10 AC890PX AC Drive VALUE INPUT BREAK VALUE INPUT LOSS LEVEL BREAK ENABLE BREAK TYPE UNPROCESSED ...
Страница 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Страница 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...
Страница 391: ...D 151 Programming AC890PX AC Drive Speed Rated Speed No Load Speed synchronous speed Rated Torque Torque ...