![Parker AC890PX Series Скачать руководство пользователя страница 338](http://html1.mh-extra.com/html/parker/ac890px-series/ac890px-series_product-manual_755704338.webp)
Programming
D-98
AC890PX AC Drive
PATTERN GEN
SETUP::MOTOR CONTROL::PATTERN GEN
Designed for all Motor Control Modes.
The pattern generator function block allows you to configure the Drive PWM (Pulse Width Modulator) operation.
Parameter Descriptions
RANDOM PATTERN
PREF: 73.01
Default: TRUE
Range: FALSE / TRUE
Designed for all Motor Control Modes, except when the speed feedback is a resolver.
This parameter selects between random pattern (quiet motor noise) or the more conventional fixed carrier PWM strategies.
When TRUE, random pattern is enabled.
FREQ SELECT
PREF: 73.02
Default: 3000 Hz
Range: 2000 to 6000 Hz
For AC induction Motor control modes, except when the speed feedback is a resolver:
This parameter selects the PWM switching frequency of the output power stack.
The higher the switching frequency, the lower the level of motor audible noise. However, this is only achieved at the
expense of increased drive losses and reduced stack current rating.
For PMAC control mode with an ENdat encoder fitted :
This parameter selects the PWM switching frequency of the output power stack if the parameter PWM FREQ PMAC is set
to ‘OTHERS’. The max value is limited to 4000Hz.
The higher the switching frequency, the lower the level of motor audible noise. However, this is only achieved at the
expense of increased drive losses and reduced stack current rating.
DEFLUX DELAY
PREF: 73.03
Default: 2.0 s
Range: 0.1 to 10.0 s
Designed for all Motor Control Modes, except PMAC Control Mode.
Sets the minimum allowed delay between disabling and then re-enabling PWM production (i.e. stopping and starting the drive).
Содержание AC890PX Series
Страница 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Страница 25: ...3 4 Installing the Drive AC890PX AC Drive Outline Drawing of AC890PX 132kW 400kW HC471581 page 2 of 2 ...
Страница 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Страница 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Страница 159: ...7 24 The Keypad AC890PX AC Drive Assembly Procedure Mounting Dimensions for the Remote Mounted 6901 Keypad ...
Страница 250: ...Programming D 10 AC890PX AC Drive VALUE INPUT BREAK VALUE INPUT LOSS LEVEL BREAK ENABLE BREAK TYPE UNPROCESSED ...
Страница 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Страница 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...
Страница 391: ...D 151 Programming AC890PX AC Drive Speed Rated Speed No Load Speed synchronous speed Rated Torque Torque ...