![Parker AC890PX Series Скачать руководство пользователя страница 295](http://html1.mh-extra.com/html/parker/ac890px-series/ac890px-series_product-manual_755704295.webp)
D-55
Programming
AC890PX AC Drive
Parameter Descriptions
ENERGY SAVING
PREF: 21.09
Default: FALSE
Range: FALSE / TRUE
When set TRUE, the demanded volts are reduced to minimise energy consumption if the drive is operating in a steady state at
light load.
USER FREQ 1 to 10
PREF: 21.10, 21.12, 21.14,
21.16, 21.18, 21.20, 21.22,
21.24, 21.26,21.28
Default: Refer to Parameter
Table
Range: 0.0 to 100.0 %
These parameters provide 10 frequency points, which together with the USER VOLTAGE parameters, provide the user defined
voltage profile. (USER FREQ n, USER VOLTAGE n) provide up to 10 (x,y) points on this profile. The USER FREQ
parameters are defined as a percentage of the BASE FREQUENCY parameter (refer to the MOTOR INDUCTION function
block).
USER VOLTAGE 1 to 10
PREF: 21.9, 21.11, 21.13,
21.15, 21.17, 21.19, 21.21,
21.23, 21.25,21.27, 21.29
Default: Refer to Parameter
Table
Range: 0.0 to 100.0 %
These parameters provide 10 voltage points, which together with the USER FREQ parameters, provide the user defined voltage
profile. (USER FREQ n, USER VOLTAGE n) provide up to 10 (x,y) points on this profile. The USER VOLTAGE parameters
are defined as a percentage of the MOTOR VOLTAGE parameter (refer to the MOTOR INDUCTION function block).
Содержание AC890PX Series
Страница 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Страница 25: ...3 4 Installing the Drive AC890PX AC Drive Outline Drawing of AC890PX 132kW 400kW HC471581 page 2 of 2 ...
Страница 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Страница 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Страница 159: ...7 24 The Keypad AC890PX AC Drive Assembly Procedure Mounting Dimensions for the Remote Mounted 6901 Keypad ...
Страница 250: ...Programming D 10 AC890PX AC Drive VALUE INPUT BREAK VALUE INPUT LOSS LEVEL BREAK ENABLE BREAK TYPE UNPROCESSED ...
Страница 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Страница 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...
Страница 391: ...D 151 Programming AC890PX AC Drive Speed Rated Speed No Load Speed synchronous speed Rated Torque Torque ...