Sequencing Logic
B-10
AC890PX AC Drive
Communications Status
The COMMS STATUS parameter (PREF 95.08) in the COMMS CONTROL function block monitors the sequencing of the
Drive. It is a 16-bit word based on standard fieldbus drive profiles. Some bits are not implemented in the initial release and
are set to 0 (see “Supported” column of the table below).
Bit Name
Description
Supported
0
Ready To Switch On
1
Switched On
Ready for operation (refer control bit 0)
2
Operation Enabled
(refer control bit 3)
3
Fault
Tripped
4
(Not) Voltage Disabled
OFF 2 Command pending
5
(Not) Quick Stop
OFF 3 Command pending
6
Switch On Disable
Switch On Inhibited
7
Warning
8
SP / PV in Range
9
Remote
= 1 if Drive will accept Command Word
10
Setpoint Reached
= 1 if not ramping
11
Internal Limit Active
= 1 if current limit active or speed loop is in torque limit
12
13
14
15
Содержание AC890PX Series
Страница 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Страница 25: ...3 4 Installing the Drive AC890PX AC Drive Outline Drawing of AC890PX 132kW 400kW HC471581 page 2 of 2 ...
Страница 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Страница 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Страница 159: ...7 24 The Keypad AC890PX AC Drive Assembly Procedure Mounting Dimensions for the Remote Mounted 6901 Keypad ...
Страница 250: ...Programming D 10 AC890PX AC Drive VALUE INPUT BREAK VALUE INPUT LOSS LEVEL BREAK ENABLE BREAK TYPE UNPROCESSED ...
Страница 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Страница 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...
Страница 391: ...D 151 Programming AC890PX AC Drive Speed Rated Speed No Load Speed synchronous speed Rated Torque Torque ...