3-26
Installing the Drive
AC890PX AC Drive
DIGITAL I/O
Name
Range
Description
X16
01
DOUT4A
open/closed
Normally-open relay contacts, A & B.
02
DOUT4B
open/closed
Default function DOUT4 closed = healthy
03
DOUT5A
open/closed
Normally-open relay contacts, A & B.
04
DOUT5B
open/closed
Default function DOUT5 closed = running
05
DOUT6A
open/closed
Normally-open relay contacts, A & B.
06
DOUT6B
open/closed
No default function.
07
-
-
UNUSED
08
MTR THERM A
-
Motor Thermistor, or link terminals X16/08 & X16/09
09
MTR THERM B
-
Motor Thermistor, or link terminals X16/08 & X16/09
All digital inputs/outputs are configurable using the DSE 890 (Drive System Explorer) Configuration Tool supplied on disk.
The table shows the factory defaults. The digital inputs require 24V DC which is supplied at terminal X14/03. For further
information refer to the DSE 890 Configuration Tool.
Relay outputs are volt-free, normally open contacts. Rated to 240V 3A resistive load. Alternatively they may be used down to
1mA, 12V levels.
Содержание AC890PX Series
Страница 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Страница 25: ...3 4 Installing the Drive AC890PX AC Drive Outline Drawing of AC890PX 132kW 400kW HC471581 page 2 of 2 ...
Страница 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Страница 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Страница 159: ...7 24 The Keypad AC890PX AC Drive Assembly Procedure Mounting Dimensions for the Remote Mounted 6901 Keypad ...
Страница 250: ...Programming D 10 AC890PX AC Drive VALUE INPUT BREAK VALUE INPUT LOSS LEVEL BREAK ENABLE BREAK TYPE UNPROCESSED ...
Страница 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Страница 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...
Страница 391: ...D 151 Programming AC890PX AC Drive Speed Rated Speed No Load Speed synchronous speed Rated Torque Torque ...