Programming
D-68
AC890PX AC Drive
Parameter Descriptions
UP TIME
PREF: 162.04
Default: 1.0 s
Range: 0.5 to 10.0s
Determines the rated at which the inverse time current limit is ramped back to the minimum value between 200% of
permanent drive current and MAX CURRENT (refer to MOTOR PMAC 1 Function Block) once the overload is removed.
IT LIMITING
PREF: 162.05
Default: FALSE
Range: FALSE / TRUE
This diagnostic indicates if the inverse time current limit is active.
INVERSE TIME OP
PREF: 162.06
Default: —.00 %
Range: —.00 %
This diagnostic indicates the present level of current that is allowed as a percentage of STACK CURRENT (refer to the
FEEDBACKS function block), clamped by MAX CURRENT (refer to the MOTOR PMAC 1 function block). Under normal
conditions and when not clamped by MAX CURRENT, this ranges from 110% to 200% of STACK CURRENT, depending
on the frame size and mode as described below. When the drive is limiting, this value will be the AIMING POINT clamped
by either 105% of STACK CURRENT or PERM CURRENT (refer to the MOTOR PMAC 1 function block).
In Quadratic Torque Mode:
Under normal conditions, the drive current limit is set to 110% of STACK CURRENT.
For Frames B, C & D:
Under normal conditions, the drive current limit is et to 200% of STACK CURRENT and DELAY is limited to 4
seconds.
For Mobile Frames:
Under normal conditions, the drive current limit is set to 175% of STACK CURRENT.
For Other Frame Sizes:
Under normal conditions, the drive current limit is set to 150% of STACK CURRENT.
IT WARNING
PREF: 162.07
Default: FALSE
Range: FALSE/TRUE
This diagnostic indicates if the reduction is acting or not.
Содержание AC890PX Series
Страница 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Страница 25: ...3 4 Installing the Drive AC890PX AC Drive Outline Drawing of AC890PX 132kW 400kW HC471581 page 2 of 2 ...
Страница 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Страница 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Страница 159: ...7 24 The Keypad AC890PX AC Drive Assembly Procedure Mounting Dimensions for the Remote Mounted 6901 Keypad ...
Страница 250: ...Programming D 10 AC890PX AC Drive VALUE INPUT BREAK VALUE INPUT LOSS LEVEL BREAK ENABLE BREAK TYPE UNPROCESSED ...
Страница 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Страница 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...
Страница 391: ...D 151 Programming AC890PX AC Drive Speed Rated Speed No Load Speed synchronous speed Rated Torque Torque ...