Programming
D-164
AC890PX AC Drive
STALL TRIP
SETUP::TRIPS::STALL TRIP
The function block protects the motor from damage that may be caused by continuous operation beyond specification (i.e. in a
stalled condition).
Parameter Descriptions
STALL TIME
PREF: 105.01
Default: 120.0 s
Range: 0.1 to 3000.0 s
The time after which a stall condition will cause a trip.
STALL LIMIT TYPE
PREF: 105.03
Default: 0
Range: See below
This parameter determines whether the stall trip operates on motor torque or motor current.
Enumerated Value
:
Stall Limit Type
0 : TORQUE
1 : CURRENT
Functional Description
If STALL LIMIT TYPE is set to TORQUE and the estimated load exceeds the active TORQUE LIMIT (refer to the TORQUE
LIMIT function block) for a time greater than STALL TIME then the stall trip will become active. The timer is reset whenever
the estimated load is less than the active Torque Limit.
Similarly, if the STALL LIMIT TYPE is set to CURRENT and the measured current exceeds the active Current limit (i.e. the
drive is in current limit) for a time greater than STALL TIME then the stall trip will become active. The timer is reset
whenever the measured current is less than the active Current Limit.
Refer to Chapter 11 for a description of the trips supported by the Drive.
Содержание AC890PX Series
Страница 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Страница 25: ...3 4 Installing the Drive AC890PX AC Drive Outline Drawing of AC890PX 132kW 400kW HC471581 page 2 of 2 ...
Страница 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Страница 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Страница 159: ...7 24 The Keypad AC890PX AC Drive Assembly Procedure Mounting Dimensions for the Remote Mounted 6901 Keypad ...
Страница 250: ...Programming D 10 AC890PX AC Drive VALUE INPUT BREAK VALUE INPUT LOSS LEVEL BREAK ENABLE BREAK TYPE UNPROCESSED ...
Страница 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Страница 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...
Страница 391: ...D 151 Programming AC890PX AC Drive Speed Rated Speed No Load Speed synchronous speed Rated Torque Torque ...