![Parker AC890PX Series Скачать руководство пользователя страница 174](http://html1.mh-extra.com/html/parker/ac890px-series/ac890px-series_product-manual_755704174.webp)
Keypad Menus
8-15
AC890PX AC Drive
QUICK SETUP MENU
PREF
6911 Display
Description
Range
Default
70.01
QUADRATIC TORQUE
TIME (s)
150%
% OF RATED MOTOR CURRENT
30
60
100% overload for 30s (Heavy Duty)
127.5%
105%
100%
FALSE - CONSTANT: Inverse time allows 150%
overload for 60s, then ramps back the current limit to
105% over a 10s period. At a lower load, the
overload area remains the same, e.g. at 127.5% load
for 120s - after 120s has expired, the output of the
inverse time function is ramped back over a 10s
period from 150% as before.
TRUE - QUADRATIC: current limit is set to 110%
motor current, inverse time delay is set to 30s
0=FALSE
1=TRUE
0
70.13
* MOTOR CURRENT
This parameter contains the motor nameplate full-
load line current
0.01 to 999.99A
product
code
dependent
Содержание AC890PX Series
Страница 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Страница 25: ...3 4 Installing the Drive AC890PX AC Drive Outline Drawing of AC890PX 132kW 400kW HC471581 page 2 of 2 ...
Страница 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Страница 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Страница 159: ...7 24 The Keypad AC890PX AC Drive Assembly Procedure Mounting Dimensions for the Remote Mounted 6901 Keypad ...
Страница 250: ...Programming D 10 AC890PX AC Drive VALUE INPUT BREAK VALUE INPUT LOSS LEVEL BREAK ENABLE BREAK TYPE UNPROCESSED ...
Страница 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Страница 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...
Страница 391: ...D 151 Programming AC890PX AC Drive Speed Rated Speed No Load Speed synchronous speed Rated Torque Torque ...