D-9
Programming
AC890PX AC Drive
Parameter Descriptions
VALUE
PREF: 1.06, 2.06, 3.06, 4.06,
5.06, 179.06
Default: —.xx %
Range: —.xx %
The input reading. (PREF 5.06 is ANIN5, PREF 179.06 is ANIN6, see the Functional Description).
FITTED
PREF: 179.08
Default:
Range: FALSE / TRUE
Only available on ANIN6. This diagnostic indicates if the 8903/AI option board is fitted on the drive. Diagnostic is FALSE if
the board is not fitted, otherwise it is TRUE.
When FITTED = FALSE, the ANIN6 VALUE is reset to 0.0000 %.
Functional Description
The Drive has four analog inputs. There is an analog input function block for each:
AIN1 is associated with the signal on terminal X12/02
AIN2 is associated with the signal on terminal X12/03
AIN3 is associated with the signal on terminal X12/04
AIN4 is associated with the signal on terminal X12/05
Analog input 5 is a special case: terminals AIN1 and AIN2 can be used as a differential
10V input (which we call AIN5).
Analog input 6 is also a special case. It is a high resolution differential analog input (15-bit + sign) located on the 8903/AI
option board. The input type is -10. +10 V.
All analog inputs can be configured as a direct input into the Speed Loop providing a fast speed or torque demand for servos.
The input voltage is pre-processed and converted into a numeric value by the analog input electronics of the Drive. The analog
input function blocks further process this reading so that a value of 0.00% represents an input equal to the low input range,
while a value of 100.00% represents an input equal to the high input range.
The break detect facility may only be used in conjunction with the 4..20mA hardware range. An input break is defined as an
input reading less than 0.45mA. When an input break has been detected, the VALUE output is forced to be the BREAK
VALUE.
Содержание AC890PX Series
Страница 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Страница 25: ...3 4 Installing the Drive AC890PX AC Drive Outline Drawing of AC890PX 132kW 400kW HC471581 page 2 of 2 ...
Страница 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Страница 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Страница 159: ...7 24 The Keypad AC890PX AC Drive Assembly Procedure Mounting Dimensions for the Remote Mounted 6901 Keypad ...
Страница 250: ...Programming D 10 AC890PX AC Drive VALUE INPUT BREAK VALUE INPUT LOSS LEVEL BREAK ENABLE BREAK TYPE UNPROCESSED ...
Страница 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Страница 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...
Страница 391: ...D 151 Programming AC890PX AC Drive Speed Rated Speed No Load Speed synchronous speed Rated Torque Torque ...