D-23
Programming
AC890PX AC Drive
DIGITAL INPUT
SETUP::INPUTS & OUTPUTS::DIGITAL INPUT
The digital input block converts the physical input voltage to TRUE or FALSE control signals.
Parameter Descriptions
VALUE
PREF: 8.02, 9.02, 10.02, 11.02,
12.02, 13.02, 14.02, 15.02,
16.02
Default: FALSE
Range: FALSE / TRUE
The TRUE or FALSE input.
Functional Description
There is a DIGITAL INPUT function block associated with each of the following terminals:
The Control Board has nine configurable digital inputs:
DIN1 is associated with terminal X15/01
DIN2 is associated with terminal X15/02
DIN3 is associated with terminal X15/03
DIN4 is associated with terminal X15/04
DIN5 is associated with terminal X15/05
DIN6 is associated with terminal X15/06
DIN7 is associated with terminal X15/07
DIN8 is associated with terminal X15/08
DIN9 is associated with terminal X15/09
Terminals X15/08 and X15/09 act as inputs by default. These terminals can also be set as outputs. Refer to DIGITAL
OUTPUT, page D-24.
Содержание AC890PX Series
Страница 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Страница 25: ...3 4 Installing the Drive AC890PX AC Drive Outline Drawing of AC890PX 132kW 400kW HC471581 page 2 of 2 ...
Страница 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Страница 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Страница 159: ...7 24 The Keypad AC890PX AC Drive Assembly Procedure Mounting Dimensions for the Remote Mounted 6901 Keypad ...
Страница 250: ...Programming D 10 AC890PX AC Drive VALUE INPUT BREAK VALUE INPUT LOSS LEVEL BREAK ENABLE BREAK TYPE UNPROCESSED ...
Страница 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Страница 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...
Страница 391: ...D 151 Programming AC890PX AC Drive Speed Rated Speed No Load Speed synchronous speed Rated Torque Torque ...