![Parker AC890PX Series Скачать руководство пользователя страница 468](http://html1.mh-extra.com/html/parker/ac890px-series/ac890px-series_product-manual_755704468.webp)
Programming
D-228
AC890PX AC Drive
2
PREF
Name
Block
Type
Range
Default
ro\rw
Notes
98.04
INPUT 2 BREAK
I/O TRIPS
BOOL
0 : FALSE
1 : TRUE
FALSE
rw
98.05
THERMISTOR
I/O TRIPS
BOOL
0 : FALSE
1 : TRUE
FALSE
ro
Output
98.06
ENCODER
I/O TRIPS
BOOL
0 : FALSE
1 : TRUE
FALSE
ro
Output
98.07
EXTERNAL TRIP
I/O TRIPS
BOOL
0 : FALSE
1 : TRUE
FALSE
ro
Output
98.08
EXT TRIP MODE
I/O TRIPS
ENUM
0 : TRIP
1 : COAST
2 : DISABLED
DISABLED
rw
98.09
COMMS BREAK
I/O TRIPS
BOOL
0 : FALSE
1 : TRUE
FALSE
rw
98.10
INPUT 1 NAME
I/O TRIPS
STRING max length is 16 chars
rw
98.11
INPUT 2 NAME
I/O TRIPS
STRING max length is 16 chars
rw
98.12
STO ACTIVE
I/O TRIPS
BOOL
0 : FALSE
1 : TRUE
FALSE
ro
Output
99.01
ENABLE
DYNAMIC BRAKING BOOL
0 : FALSE
1 : TRUE
TRUE
rw
99.03
BRAKE
RESISTANCE
DYNAMIC BRAKING REAL
0.01 to 300.00 Ohm
100.00 Ohm
rw
2,3
99.04
BRAKE POWER
DYNAMIC BRAKING REAL
0.1 to 510.0 kW
0.1 kW
rw
2,3
99.05
1SEC OVER RATING DYNAMIC BRAKING REAL
1 to 40
25
rw
2,3
99.06
BRAKING
DYNAMIC BRAKING BOOL
0 : FALSE
1 : TRUE
FALSE
ro
Output
99.07
INT DB RESISTOR
DYNAMIC BRAKING BOOL
0 : FALSE
1 : TRUE
FALSE
rw
3
100.01 RAMP TYPE
REFERENCE RAMP ENUM
0 : LINEAR
1 : S
LINEAR
rw
100.02 ACCEL TIME
REFERENCE RAMP REAL
0.0 to 3000.0 s
20.0 s
rw
3
Содержание AC890PX Series
Страница 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Страница 25: ...3 4 Installing the Drive AC890PX AC Drive Outline Drawing of AC890PX 132kW 400kW HC471581 page 2 of 2 ...
Страница 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Страница 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Страница 159: ...7 24 The Keypad AC890PX AC Drive Assembly Procedure Mounting Dimensions for the Remote Mounted 6901 Keypad ...
Страница 250: ...Programming D 10 AC890PX AC Drive VALUE INPUT BREAK VALUE INPUT LOSS LEVEL BREAK ENABLE BREAK TYPE UNPROCESSED ...
Страница 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Страница 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...
Страница 391: ...D 151 Programming AC890PX AC Drive Speed Rated Speed No Load Speed synchronous speed Rated Torque Torque ...