![Parker AC890PX Series Скачать руководство пользователя страница 54](http://html1.mh-extra.com/html/parker/ac890px-series/ac890px-series_product-manual_755704054.webp)
Installing the Drive
3-33
AC890PX AC Drive
SET-UP PARAMETERS
PREF
6911Display
Default
Brief Description
V/Hz
SV
CLV
4-Q PMAC
102.01 RUN STOP MODE
0 : RUN RAMP
1 : COAST
2 : DC INJECTION
3 : STOP RAMP
Selects the stopping mode
used by the drive
x
x
x
x
x
103.01 JOG SETPOINT
10.0 %
Drive speed setpoint whilst
jogging (percentage of
MAX SPEED)
x
x
x
x
x
21.01 V/F SHAPE
0 : LINEAR LAW
1 : FAN LAW
2 : USER DEFINED
Sets the type of volts to
frequency template that is
used to flux the motor
x
70.01 QUADRATIC
TORQUE
0 : FALSE
1 : TRUE
0 : FALSE = Constant
Selects between Constant
or Quadratic mode of
operation
x
x
x
x
27.05 MOTOR CURRENT product code dependent Enter the motor full load
current from the motor
nameplate
x
x
x
x
21.03 FIXED BOOST
product code dependent Boosts starting torque by
adding volts at low speed
x
82.01 CURRENT LIMIT
150.00%
Level of motor current as %
of FULL LOAD CALIB
x
x
x
x
81.01 VOLTAGE MODE
None
Defines how volts Hz
characteristic varies in
response to changes in DC
link voltage.
x
x
x
x
27.02 POWER
product code dependent Nameplate induction
motor power
x
x
x
Содержание AC890PX Series
Страница 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Страница 25: ...3 4 Installing the Drive AC890PX AC Drive Outline Drawing of AC890PX 132kW 400kW HC471581 page 2 of 2 ...
Страница 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Страница 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Страница 159: ...7 24 The Keypad AC890PX AC Drive Assembly Procedure Mounting Dimensions for the Remote Mounted 6901 Keypad ...
Страница 250: ...Programming D 10 AC890PX AC Drive VALUE INPUT BREAK VALUE INPUT LOSS LEVEL BREAK ENABLE BREAK TYPE UNPROCESSED ...
Страница 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Страница 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...
Страница 391: ...D 151 Programming AC890PX AC Drive Speed Rated Speed No Load Speed synchronous speed Rated Torque Torque ...