Programming
D-194
AC890PX AC Drive
2
PREF
Name
Block
Type
Range
Default
ro\rw
Notes
27.09
MOTOR POLES
MOTOR
INDUCTION
ENUM
0 : 2 POLE
1 : 4 POLE
2 : 6 POLE
3 : 8 POLE
4 : 10 POLE
5 : 12 POLE
4 POLE
rw
27.10
POWER FACTOR
MOTOR
INDUCTION
REAL
0.50 to 0.99
0.86
rw
3
27.11
OVERLOAD
MOTOR
INDUCTION
REAL
1.0 to 5.0
2.0
rw
3
27.14
STATOR RES
MOTOR
INDUCTION
REAL
0.0000 to 250.0000 Ohm 0.2851 Ohm
rw
3,5
27.15
LEAKAGE INDUC
MOTOR
INDUCTION
REAL
0.00 to 300.00 mH
9.08 mH
rw
3,5
27.16
MUTUAL INDUC
MOTOR
INDUCTION
REAL
0.00 to 3000.00 mH
36.30 mH
rw
3,5
27.17
ROTOR TIME
CONST
MOTOR
INDUCTION
REAL
10.00 to 30000.00 ms
506.08 ms
rw
3,5
27.23
TOTAL INERTIA
MOTOR
INDUCTION
REAL
0.0000 to 300.0000
kgm2
0.0000 kgm2
rw
5
29.01
DEFLUX TIME
INJ BRAKING
REAL
0.1 to 20.0 s
1.0 s
rw
3,5
29.02
FREQUENCY
INJ BRAKING
REAL
1.0 to 500.0 Hz
6.0 Hz
rw
3,5
29.03
I-LIM LEVEL
INJ BRAKING
REAL
50.00 to 150.00 %
100.00 %
rw
29.04
DC PULSE
INJ BRAKING
REAL
0.0 to 100.0 s
2.0 s
rw
3,5
29.05
FINAL DC PULSE
INJ BRAKING
REAL
0.0 to 10.0 s
3.0 s
rw
3,5
29.06
DC LEVEL
INJ BRAKING
REAL
0.00 to 25.00 %
1.25 %
rw
3,5
29.07
TIMEOUT
INJ BRAKING
REAL
0.0 to 600.0 s
90.0 s
rw
29.08
BASE VOLTS
INJ BRAKING
REAL
0.00 to 115.47 %
75.00 %
rw
3,5
29.09
ACTIVE
INJ BRAKING
BOOL
0 : FALSE
1 : TRUE
FALSE
ro
Output
Содержание AC890PX Series
Страница 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Страница 25: ...3 4 Installing the Drive AC890PX AC Drive Outline Drawing of AC890PX 132kW 400kW HC471581 page 2 of 2 ...
Страница 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Страница 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Страница 159: ...7 24 The Keypad AC890PX AC Drive Assembly Procedure Mounting Dimensions for the Remote Mounted 6901 Keypad ...
Страница 250: ...Programming D 10 AC890PX AC Drive VALUE INPUT BREAK VALUE INPUT LOSS LEVEL BREAK ENABLE BREAK TYPE UNPROCESSED ...
Страница 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Страница 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...
Страница 391: ...D 151 Programming AC890PX AC Drive Speed Rated Speed No Load Speed synchronous speed Rated Torque Torque ...