55
lowed by the one to combine the execution condition resulting from the first
logic block instruction and the execution condition of the logic block third from
the end, and on back to the first logic block that is being combined.
00000 00001
00002 00003
00502
00004 00202
Block
a
Block
b
Block
b2
Block
b1
Address
Instruction
Operands
00000
LD NOT
00000
00001
AND
00001
00002
LD
00002
00003
AND NOT
00003
00004
LD NOT
00004
00005
AND
00202
00006
OR LD
—
00007
AND LD
—
00008
OUT
00502
When determining what logic block instructions will be required to code a dia-
gram, it is sometimes necessary to break the diagram into large blocks and
then continue breaking the large blocks down until logic blocks that can be
coded without logic block instructions have been formed. These blocks are
then coded, combining the small blocks first, and then combining the larger
blocks. Either AND LOAD or OR LOAD is used to combine the blocks, i.e.,
AND LOAD or OR LOAD always combines the last two execution conditions
that existed, regardless of whether the execution conditions resulted from a
single condition, from logic blocks, or from previous logic block instructions.
When working with complicated diagrams, blocks will ultimately be coded
starting at the top left and moving down before moving across. This will gen-
erally mean that, when there might be a choice, OR LOAD will be coded be-
fore AND LOAD.
The following diagram must be broken down into two blocks and each of
these then broken into two blocks before it can be coded. As shown below,
blocks a and b require an AND LOAD. Before AND LOAD can be used, how-
ever, OR LOAD must be used to combine the top and bottom blocks on both
sides, i.e., to combine a1 and a2; b1 and b2.
00000 00001
00004 00005
00503
Block
a
Block
b
00006 00007
Block
b2
Block
b1
00002 00003
Block
a2
Block
a1
Blocks a1 and a2
Blocks b1 and b2
Blocks a and b
Address
Instruction
Operands
00000
LD
00000
00001
AND NOT
00001
00002
LD NOT
00002
00003
AND
00003
00004
OR LD
—
00005
LD
00004
00006
AND
00005
00007
LD
00006
00008
AND
00007
00009
OR LD
—
00010
AND LD
—
00011
OUT
00503
The following type of diagram can be coded easily if each block is coded in
order: first top to bottom and then left to right. In the following diagram,
Complicated Diagrams
Basic Ladder Diagrams
Section 4-3
Содержание SYSMAC C200H
Страница 1: ...OPERATION MANUAL C200H CPU01 E 03 E 11 E SYSMAC Programmable Controllers Cat No W130 E1 05 ...
Страница 2: ...C200H Programmable Controllers CPU01 E 03 E 11 E Operation Manual Revised June 2003 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 8: ...TABLE OF CONTENTS ix Glossary 345 Index 363 Revision History 369 ...
Страница 342: ...336 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage ...
Страница 374: ...Cat No W130 E1 05 C200H Programmable Controllers CPU01 E 03 E 11 E OPERATION MANUAL ...