![Omron SYSMAC C200H Скачать руководство пользователя страница 150](http://html1.mh-extra.com/html/omron/sysmac-c200h/sysmac-c200h_operation-manual_742423150.webp)
137
5-14-6
BLOCK TRANSFER – XFER(70)
N: Number of words (BCD)
IR, SR, AR, DM, HR, TC, LR, #
S: Starting source word
IR, SR, AR, DM, HR, TC, LR
Ladder Symbols
Operand Data Areas
D: Starting destination word
IR, AR, DM, HR, TC, LR
XFER(70)
N
S
D
@XFER(70)
N
S
D
Both S and D may be in the same data area, but their respective block areas
must not overlap. S and S+N must be in the same data area, as must D and
D+N.
When the execution condition is OFF, XFER(70) is not executed. When the
execution condition is ON, XFER(70) copies the contents of S, S+1, ..., S+N
to D, D+1, ..., D+N.
2
D
3 4 5
1
D+1
3 4 5
2
D+2
3 4 2
2
D+N
6 4 5
2
S
3 4 5
1
S+1
3 4 5
2
S+2
3 4 2
2
S+N
6 4 5
Flags
ER:
N is not BCD
S and S+N or D and D+N are not in the same data area.
Indirectly addressed DM word is non-existent. (Content of
*
DM word
is not BCD, or the DM area boundary has been exceeded.)
5-14-7
DATA EXCHANGE – XCHG(73)
E1: Exchange word 1
IR, AR, DM, HR, TC, LR
E2: Exchange word 2
IR, AR, DM, HR, TC, LR
Ladder Symbols
Operand Data Areas
XCHG(73)
E1
E2
@XCHG(73)
E1
E2
Limitations
Description
Data Movement
Section 5-14
Содержание SYSMAC C200H
Страница 1: ...OPERATION MANUAL C200H CPU01 E 03 E 11 E SYSMAC Programmable Controllers Cat No W130 E1 05 ...
Страница 2: ...C200H Programmable Controllers CPU01 E 03 E 11 E Operation Manual Revised June 2003 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 8: ...TABLE OF CONTENTS ix Glossary 345 Index 363 Revision History 369 ...
Страница 342: ...336 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage ...
Страница 374: ...Cat No W130 E1 05 C200H Programmable Controllers CPU01 E 03 E 11 E OPERATION MANUAL ...