Appendix B
Programming Instructions
291
IR
SR
HR
TR
AR
LR
TC
DM
#
00000 to 23515
23600 to 25507
HR 0000 to 9915
TR 0 to 7
AR 0000 to 2715
LR 0000 to 6315
TC 000 to 511
Read/Wr: DM 0000 to DM 0999
Rd only: DM 1000 to DM 1999
0000 to 9999
or 0000 to FFFF
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
Data Areas
Special Instructions
Name
Mnemonic
Symbol
Function
Operand Data Areas
NO OPERATION
NOP(00)
None
Nothing is executed and program opera-
tion moves to the next instruction.
None
END
END(01)
END(01)
Required at the end of each program. In-
structions located after END(01) will not be
executed.
None
INTERLOCK
IL(02)
INTERLOCK CLEAR
ILC(03)
IL(02)
ILC(03)
If an interlock condition is OFF, all outputs
and all timer PVs between the current
IL(02) and the next ILC(03) are turned OFF
or reset, respectively. Other instructions
are treated as NOP. Counter PVs are main-
tained. If the execution condition is ON, ex-
ecution continues normally.
None
JUMP
JMP(04)
JUMP END
JME(05)
N
JMP(04)
JME(05)
N
When the execution condition for the
JMP(04) instruction is ON, all instructions
between JMP(04) and the corresponding
JME(05) are to be ignored or treated as
NOP(00). For direct jumps, the corre-
sponding JMP(04) and JME(05) instruc-
tions have the same N value in the range
01 through 99. Direct jumps are usable
only once each per program (i.e., N is 01
through 99 can be used only once each)
and the instructions between the JUMP
and JUMP END instructions are ignored;
00 may be used as many times as neces-
sary, instructions between JMP 00 and the
next JME 00 are treated as NOP, thus in-
creasing cycle time, as compared with di-
rect jumps.
N:
00 to 99
(not applicable for
C
__
P, C
__
K, or
C120 PCs)
FAILURE ALARM
(@)FAL(06)
FAL(06)
N
Assigns a failure alarm code to the given
execution condition.When N can be given
a value between 01 and 99 to indicate that
a non-fatal error (i.e., one that will not stop
the CPU) has occurred. This is indicated
by the PC outputting N (the FAL number)
to the FAL output area. To reset the FAL
area, N can be defined as 00. This will
cause all previously recorded FAL num-
bers in the FAL area to be deleted. FAL
data sent after a 00 will be recorded in the
normal way. The same code numbers can
be used for both FAL(06) and FALS(07).
N:
00 to 99
SEVERE FAILURE
ALARM
FALS(07)
FALS(07) N
A fatal error is indicated by outputting N to
the FAL output area and the CPU is
stopped. The same FAL numbers are used
for both FAL(06) and FALS(07).
N:
01 to 99
Содержание SYSMAC C200H
Страница 1: ...OPERATION MANUAL C200H CPU01 E 03 E 11 E SYSMAC Programmable Controllers Cat No W130 E1 05 ...
Страница 2: ...C200H Programmable Controllers CPU01 E 03 E 11 E Operation Manual Revised June 2003 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 8: ...TABLE OF CONTENTS ix Glossary 345 Index 363 Revision History 369 ...
Страница 342: ...336 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage ...
Страница 374: ...Cat No W130 E1 05 C200H Programmable Controllers CPU01 E 03 E 11 E OPERATION MANUAL ...