145
Limitations
Can be performed with the CPU11-E only.
When the execution condition is OFF, CMPL(60) is not executed. When the
execution condition is ON, CMPL(60) joins the 4-digit hexadecimal content of
Cp1+1 with that of Cp1, and that of Cp2+1 with that of Cp2 to create two
8-digit hexadecimal numbers, Cp+1,Cp1 and Cp2+1,Cp2. The two 8-digit
numbers are then compared and the result is output to the GR, EQ, and LE
flags in the SR area.
Placing other instructions between CMPL(60) and the operation which ac-
cesses the EQ, LE, and GR flags may change the status of these flags. Be
sure to access them before the desired status is changed.
Flags
ER:
Indirectly addressed DM word is non-existent. (Content of
*
DM word
is not BCD, or the DM area boundary has been exceeded.)
GR:
ON if Cp1+1,Cp1 is greater than Cp2+1,Cp2.
EQ:
ON if Cp1+1,Cp1 equals Cp2+1,Cp2.
LE:
ON if Cp1+1,Cp1 is less than Cp2+1,Cp2.
The following example shows how to save the comparison result immedi-
ately. If the content of HR 10, HR 09 is greater than that of 011, 010, then
00200 is turned ON; if the two contents are equal, 00201 is turned ON; if
content of HR 10, HR 09 is less than that of 011, 010, then 00202 is turned
ON. In some applications, only one of the three OUTs would be necessary,
making the use of TR 0 unnecessary. With this type of programming, 00200,
00201, and 00202 are changed only when CMPL(60) is executed.
CMPL(60)
010
HR 09
00000
25505
00200
25507
00202
TR
0
25506
00201
Greater Than
Equal
Less Than
---
Address
Instruction
Operands
Address
Instruction
Operands
00000
LD
00000
00001
OUT
TR
0
00002
CMPL(60)
HR
09
010
00003
LD
TR
0
00004
AND
25505
00005
OUT
00200
00006
LD
TR
0
00007
AND
25506
00008
OUT
00201
00009
LD
TR
0
00010
AND
25507
00011
OUT
00202
Description
Precautions
Example:
Saving CMPL(60) Results
Data Comparison
Section 5-15
Содержание SYSMAC C200H
Страница 1: ...OPERATION MANUAL C200H CPU01 E 03 E 11 E SYSMAC Programmable Controllers Cat No W130 E1 05 ...
Страница 2: ...C200H Programmable Controllers CPU01 E 03 E 11 E Operation Manual Revised June 2003 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 8: ...TABLE OF CONTENTS ix Glossary 345 Index 363 Revision History 369 ...
Страница 342: ...336 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage ...
Страница 374: ...Cat No W130 E1 05 C200H Programmable Controllers CPU01 E 03 E 11 E OPERATION MANUAL ...