195
Flags
25407: Step Start Flag; turns ON for one cycle when STEP(08) is executed
and can be used to reset counters in steps as shown below if neces-
sary.
SNXT(09) 01000
CP
R
CNT 01
#0003
00000
00100
25407
STEP(08) 01000
1 Cycle
25407
01000
Start
Address
Instruction
Operands
Address
Instruction
Operands
00000
LD
00000
00001
SNXT(09)
01000
00002
STEP(08)
01000
00003
LD
00100
00004
LD
25407
00005
CNT
01
#
0003
Examples
The following three examples demonstrate the three types of execution con-
trol possible with step programming. Example 1 demonstrates sequential
execution; example 2, branching execution; and example 3, parallel execu-
tion.
The following process requires that three processes, loading, part installa-
tion, and inspection/discharge, be executed in sequence with each process
being reset before continuing on the the next process. Various sensors
(SW1, SW2, SW3, and SW4) are positioned to signal when processes are to
start and end.
SW 1
SW 2
SW 3
SW 4
Loading
Part installation
Inspection/discharge
Example 1:
Sequential Execution
Step Instructions
Section 5-21
Содержание SYSMAC C200H
Страница 1: ...OPERATION MANUAL C200H CPU01 E 03 E 11 E SYSMAC Programmable Controllers Cat No W130 E1 05 ...
Страница 2: ...C200H Programmable Controllers CPU01 E 03 E 11 E Operation Manual Revised June 2003 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 8: ...TABLE OF CONTENTS ix Glossary 345 Index 363 Revision History 369 ...
Страница 342: ...336 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage ...
Страница 374: ...Cat No W130 E1 05 C200H Programmable Controllers CPU01 E 03 E 11 E OPERATION MANUAL ...