212
send data to a node on the same Subsystem (i.e., network). Refer to the
SYSMAC NET Link System Manual for details.
Word
Bits 00 to 07
Bits 08 to 15
C
Number of words (0 to 1000 in 4-digit hexadecimal, i.e., 0000
hex
to 03E8
hex
)
C+1
Network number (0 to 127 in 2-digit
hexadecimal, i.e., 00
hex
to 7F
hex
)
Bit 14 ON: Operating level 0
OFF: Operating level 1
Bits 08 to 13 and 15: Set to 0.
C+2
Destination node (0 to 126 in 2-digit
hexadecimal, i.e., 00
hex
to 7E
hex
)*
Destination port
NSB: 00
NSU: 01/02
*The node number of the PC executing the send may be set.
SYSMAC LINK Systems
Set the destination node number to 0 to send the data to all nodes. Refer to
the SYSMAC LINK System Manual for details.
Word
Bits 00 to 07
Bits 08 to 15
C
Number of words (0 to 256 in 4-digit hexadecimal, i.e., 0000
hex
to 0100
hex
)
C+1
Response time limit (0.1 and 25.4
seconds in 2-digit hexadecimal
without decimal point, i.e., 00
hex
to
FF
hex
)
Note:
The response time will be
2 seconds if the limit is set to 0
hex
.
There will be no time limit if the
time limit is set to FF
hex
.
Bits 08 to 11:
No. of retries (0 to 15 in
hexadecimal,
i.e., 0
hex
to F
hex
)
Bit 12:
Set to 0.
Bit 13 ON: Response not returned.
OFF: Response returned.
Bit 14 ON: Operating level 0
OFF: Operating level 1
Bit 15:
Set to 1.
C+2
Destination node (0 to 62 in 2-digit
hexadecimal, i.e., 00
hex
to 3E
hex
)*
Set to 0.
*The node number of the PC executing the send cannot be set.
Examples
This example is for a SYSMAC NET Link System. When 00000 is ON, the
following program transfers the content of IR 001 through IR 005 to LR 20
through LR 24 on node 10.
0
0
0
5
0
0
0
0
0
0
0
A
IR 001
IR 002
IR 003
IR 004
IR 005
LR 20
LR 21
LR 22
LR 23
LR 24
DM 0010
DM 0011
DM 0012
15
0
SEND(90)
001
LR 20
DM 0010
00000
Node 10
Address
Instruction
Operands
00000
LD
00000
00001
SEND(90)
001
LR
20
DM
0010
Flags
ER:
The specified node number is greater than 126 in a SYSMAC NET
Link System or greater than 62 in a SYSMAC LINK System.
The sent data overruns the data area boundaries.
SYSMAC NET Link/SYSMAC LINK Instructions
Section 5-23
Содержание SYSMAC C200H
Страница 1: ...OPERATION MANUAL C200H CPU01 E 03 E 11 E SYSMAC Programmable Controllers Cat No W130 E1 05 ...
Страница 2: ...C200H Programmable Controllers CPU01 E 03 E 11 E Operation Manual Revised June 2003 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 8: ...TABLE OF CONTENTS ix Glossary 345 Index 363 Revision History 369 ...
Страница 342: ...336 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage ...
Страница 374: ...Cat No W130 E1 05 C200H Programmable Controllers CPU01 E 03 E 11 E OPERATION MANUAL ...