118
The SV of the timers can be set in the range #0000 to #9999 (BCD). If the
SV for a timer is set to #0000 or #0001, it will operate in the following way. If
the SV is set to #0000, when the timer input goes from OFF to ON, the Com-
pletion Flag will turn ON. There may be a time delay if TC 000 to TC 003 are
used. If the SV is set to #0001, because the timer accuracy is 0 to –0.1 s, the
actual time will be a value between 0 and 0.1 s, and the Completion Flag
may turn ON as soon as the timer input goes from OFF to ON. With other
values also, allow for a timer accuracy of 0 to –0.1 s when setting the SV.
Flags
ER:
SV is not in BCD.
Indirectly addressed DM word is non-existent. (Content of
*
DM word
is not BCD, or the DM area boundary has been exceeded.)
5-12-3
COUNTER – CNT
N: TC number
# (000 through 511)
Ladder Symbol
Definer Values
SV: Set value (word, BCD)
IR, AR, DM, HR, LR, #
Operand Data Areas
CP
R
CNT N
SV
Each TC number can be used as the definer in only one TIMER or COUNT-
ER instruction.
CNT is used to count down from SV when the execution condition on the
count pulse, CP, goes from OFF to ON, i.e., the present value (PV) will be
decremented by one whenever CNT is executed with an ON execution condi-
tion for CP and the execution condition was OFF for the last execution. If the
execution condition has not changed or has changed from ON to OFF, the
PV of CNT will not be changed. The Completion Flag for a counter is turned
ON when the PV reaches zero and will remain ON until the counter is reset.
CNT is reset with a reset input, R. When R goes from OFF to ON, the PV is
reset to SV. The PV will not be decremented while R is ON. Counting down
from SV will begin again when R goes OFF. The PV for CNT will not be reset
in interlocked program sections or by power interruptions.
Changes in execution conditions, the Completion Flag, and the PV are illus-
trated below. PV line height is meant only to indicate changes in the PV.
Limitations
Description
Timer and Counter Instructions
Section 5-12
Содержание SYSMAC C200H
Страница 1: ...OPERATION MANUAL C200H CPU01 E 03 E 11 E SYSMAC Programmable Controllers Cat No W130 E1 05 ...
Страница 2: ...C200H Programmable Controllers CPU01 E 03 E 11 E Operation Manual Revised June 2003 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 8: ...TABLE OF CONTENTS ix Glossary 345 Index 363 Revision History 369 ...
Страница 342: ...336 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage ...
Страница 374: ...Cat No W130 E1 05 C200H Programmable Controllers CPU01 E 03 E 11 E OPERATION MANUAL ...