The following diagram shows IL(02) being used twice with one ILC(03).
00000
00001
ILC(03)
IL(02)
00004
00005
00003
00002
IL(02)
00502
TIM 511
CP
R
CNT
001
IR 010
00100
001.5 s
TIM 511
#0015
Address
Instruction
Operands
00000
LD
00000
00001
IL(02)
00002
LD
00001
00003
TIM
511
#
0015
00004
LD
00002
00005
IL(02)
00006
LD
00003
00007
AND NOT
00004
00008
CNT
001
010
00009
LD
00005
00010
OUT
00502
00011
ILC(03)
When the execution condition for the first IL(02) is OFF, TIM 511 will be reset
to 1.5 s, CNT 001 will not be changed, and 00502 will be turned OFF. When
the execution condition for the first IL(02) is ON and the execution condition
for the second IL(02) is OFF, TIM 511 will be executed according to the
status of 00001, CNT 001 will not be changed, and 00502 will be turned OFF.
When the execution conditions for both the IL(02) are ON, the program will
execute as written.
5-9
JUMP and JUMP END – JMP(04) and JME(05)
N: Jump number
# (00 to 99)
Ladder Symbols
Definer Values
JMP(04) N
N: Jump number
# (00 to 99)
JME(05) N
Jump numbers 01 through 99 may be used only once in JMP(04) and once in
JME(05), i.e., each can be used to define one jump only. Jump number 00
can be used as many times as desired.
JMP(04) is always used in conjunction with JME(05) to create jumps, i.e., to
skip from one point in a ladder diagram to another point. JMP(04) defines the
point from which the jump will be made; JME(05) defines the destination of
the jump. When the execution condition for JMP(04) in ON, no jump is made
and the program is executed consecutively as written. When the execution
condition for JMP(04) is OFF, a jump is made to the JME(05) with the same
jump number and the instruction following JME(05) is executed next.
If the jump number for JMP(04) is between 01 and 99, jumps, when made,
will go immediately to JME(05) with the same jump number without executing
Example
Limitations
Description
JUMP and JUMP END – JMP(04) and JME(05)
Section 5-9
Содержание SYSMAC C200H
Страница 1: ...OPERATION MANUAL C200H CPU01 E 03 E 11 E SYSMAC Programmable Controllers Cat No W130 E1 05 ...
Страница 2: ...C200H Programmable Controllers CPU01 E 03 E 11 E Operation Manual Revised June 2003 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 8: ...TABLE OF CONTENTS ix Glossary 345 Index 363 Revision History 369 ...
Страница 342: ...336 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage ...
Страница 374: ...Cat No W130 E1 05 C200H Programmable Controllers CPU01 E 03 E 11 E OPERATION MANUAL ...