144
Because all of the comparisons here use to the timer’s PV as reference, the
other operand for each CMP(20) must be in 4-digit BCD.
#2000
CMP(20)
TIM 010
#3000
CMP(20)
TIM 010
CMP(20)
TIM 010
#4000
00201
00204
00202
00000
00200
25507
00200
25507
00201
25507
TIM 010
500.0 s
Output at
100 s.
Output at
200 s.
Output at
300 s.
Output at
500 s.
TIM 010
#5000
Address
Instruction
Operands
Address
Instruction
Operands
00000
LD
00000
00001
TIM
010
#
5000
00002
CMP(20)
TIM
010
#
4000
00003
AND
25507
00004
OUT
00200
00005
LD
00200
00006
CMP(20)
TIM
010
#
3000
00007
AND
25507
00008
OUT
00201
00009
LD
00201
00010
CMP(20)
TIM
010
#
2000
00011
AND
25507
00012
OUT
00202
00013
LD
TIM
010
00014
OUT
00204
5-15-3
DOUBLE COMPARE – CMPL(60)
Cp2: First word of second compare word pair
IR, SR, AR, DM, HR, TC, LR
Cp1: First word of first compare word pair
IR, SR, AR, DM, HR, TC, TR
Ladder Symbols
Operand Data Areas
CMPL(60)
Cp1
Cp2
___
Data Comparison
Section 5-15
Содержание SYSMAC C200H
Страница 1: ...OPERATION MANUAL C200H CPU01 E 03 E 11 E SYSMAC Programmable Controllers Cat No W130 E1 05 ...
Страница 2: ...C200H Programmable Controllers CPU01 E 03 E 11 E Operation Manual Revised June 2003 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 8: ...TABLE OF CONTENTS ix Glossary 345 Index 363 Revision History 369 ...
Страница 342: ...336 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage ...
Страница 374: ...Cat No W130 E1 05 C200H Programmable Controllers CPU01 E 03 E 11 E OPERATION MANUAL ...